Water stress index for data centers
Full method1,060 of 6,687 data centers (16 %) sit where the index reaches 60+: places where cooling a data center competes with scarce water, today or by 2050.
Map
Data centers coloured by their index, from green (low) to red (high). Each pie shows how many of its data centers fall in each of the five levels (hover for the counts). 103 of the 6,790 data centers are not scored because their location is approximate (town level only) or outside the Aqueduct coverage, so the map counter can exceed the 6,687 scored. Zoom in for individual sites and click one for its pillars.
How to read a score. It describes the location, not any facility's water use, which depends on its cooling (air-cooled and closed-loop sites use little water, evaporative cooling a lot). From 0 to 100, higher means scarcer water, hotter weather to cool against and more people sharing the supply; from 60 the index is called high. A country or hub figure is the median of its data centers.
Most water-stressed countries
- Pakistan7 data centers (few)score 88
- Bangladesh16 data centersscore 84
- Angola5 data centers (few)score 84
- United Arab Emirates18 data centersscore 83
- Israel16 data centersscore 72
- South Africa69 data centersscore 71
- India160 data centersscore 71
- Egypt5 data centers (few)score 71
- Peru18 data centersscore 70
- Chile51 data centersscore 68
Most water-stressed hubs
- Dhaka, Bangladesh10 data centersscore 84
- Dubai, United Arab Emirates10 data centersscore 83
- Gazipur, Bangladesh5 data centers (few)score 82
- Hyderabad, India10 data centersscore 82
- Chennai, India19 data centersscore 78
- Delhi, India21 data centersscore 76
- Phoenix, United States53 data centersscore 75
- Bologna, Italy8 data centers (few)score 73
- San Diego, United States9 data centers (few)score 73
- Madrid, Spain28 data centersscore 72
How the counts fit together: the inventory holds 8,460 facilities, of which 6,790 are data centers (the others are network points of presence or unclassified). The index is computed at the 8,357 facilities located precisely enough; its maps, rankings and medians use data centers only, 6,687 of the 6,790. The rest have a town-level location or fall outside a source's coverage.
Countries
Median over each country's data centers (≥ 5). Click a column to sort. “High” = data centers scoring ≥ 60. “Few sites” marks a median over fewer than 10 data centers, which a single site can move.
| # | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Pakistan few sites | 88 | 6 | 7 | |||||||
| 2 | Bangladesh | 84 | 15 | 16 | |||||||
| 3 | Angola few sites | 84 | 4 | 5 | |||||||
| 4 | United Arab Emirates | 83 | 18 | 18 | |||||||
| 5 | Israel | 72 | 16 | 16 | |||||||
| 6 | South Africa | 71 | 63 | 69 | |||||||
| 7 | India | 71 | 105 | 160 | |||||||
| 8 | Egypt few sites | 71 | 5 | 5 | |||||||
| 9 | Peru | 70 | 18 | 18 | |||||||
| 10 | Chile | 68 | 45 | 51 | |||||||
| 11 | Iran | 67 | 13 | 16 | |||||||
| 12 | Spain | 67 | 46 | 73 | |||||||
| 13 | Thailand | 64 | 26 | 27 | |||||||
| 14 | Belgium | 62 | 41 | 46 | |||||||
| 15 | Greece | 62 | 10 | 14 | |||||||
| 16 | México | 61 | 38 | 59 | |||||||
| 17 | Turkey | 58 | 16 | 36 | |||||||
| 18 | Portugal | 58 | 4 | 21 | |||||||
| 19 | Indonesia | 56 | 36 | 127 | |||||||
| 20 | Philippines | 56 | 5 | 31 | |||||||
| 21 | Lithuania few sites | 52 | 0 | 8 | |||||||
| 22 | Australia | 51 | 1 | 169 | |||||||
| 23 | China | 48 | 52 | 122 | |||||||
| 24 | North Macedonia few sites | 48 | 0 | 5 | |||||||
| 25 | Tanzania few sites | 48 | 1 | 8 | |||||||
| 26 | Italy | 46 | 37 | 114 | |||||||
| 27 | United Kingdom | 46 | 0 | 305 | |||||||
| 28 | Nigeria | 46 | 4 | 10 | |||||||
| 29 | Vietnam | 46 | 0 | 17 | |||||||
| 30 | Germany | 45 | 0 | 390 | |||||||
| 31 | Dominican Republic few sites | 44 | 0 | 5 | |||||||
| 32 | Hong Kong | 44 | 0 | 50 | |||||||
| 33 | Kenya | 42 | 0 | 13 | |||||||
| 34 | Japan | 40 | 0 | 155 | |||||||
| 35 | Luxembourg | 40 | 0 | 16 | |||||||
| 36 | Romania | 40 | 0 | 25 | |||||||
| 37 | Russia | 39 | 47 | 109 | |||||||
| 38 | Brazil | 39 | 0 | 250 | |||||||
| 39 | Taiwan | 39 | 0 | 21 | |||||||
| 40 | South Korea | 39 | 0 | 36 | |||||||
| 41 | United States | 37 | 285 | 2133 | |||||||
| 42 | Venezuela | 35 | 1 | 17 | |||||||
| 43 | Costa Rica few sites | 35 | 0 | 9 | |||||||
| 44 | France | 34 | 34 | 395 | |||||||
| 45 | Moldova few sites | 34 | 0 | 5 | |||||||
| 46 | Georgia few sites | 34 | 0 | 6 | |||||||
| 47 | Puerto Rico few sites | 33 | 0 | 9 | |||||||
| 48 | Estonia few sites | 32 | 0 | 7 | |||||||
| 49 | Malaysia | 31 | 0 | 47 | |||||||
| 50 | Singapore | 31 | 0 | 70 | |||||||
| 51 | Ghana few sites | 31 | 0 | 6 | |||||||
| 52 | Poland | 29 | 3 | 76 | |||||||
| 53 | Denmark | 26 | 0 | 38 | |||||||
| 54 | Croatia | 26 | 0 | 15 | |||||||
| 55 | Ireland | 24 | 0 | 90 | |||||||
| 56 | Slovenia few sites | 24 | 0 | 8 | |||||||
| 57 | Argentina | 23 | 12 | 76 | |||||||
| 58 | Ukraine | 23 | 1 | 36 | |||||||
| 59 | Finland | 23 | 0 | 53 | |||||||
| 60 | Sweden | 22 | 8 | 56 | |||||||
| 61 | Colombia | 22 | 0 | 28 | |||||||
| 62 | Serbia | 22 | 1 | 11 | |||||||
| 63 | Canada | 21 | 2 | 135 | |||||||
| 64 | Kazakhstan few sites | 21 | 0 | 8 | |||||||
| 65 | Netherlands | 20 | 0 | 214 | |||||||
| 66 | Hungary | 20 | 0 | 25 | |||||||
| 67 | Switzerland | 20 | 0 | 63 | |||||||
| 68 | Ecuador few sites | 19 | 0 | 9 | |||||||
| 69 | Bulgaria | 19 | 0 | 20 | |||||||
| 70 | Czechia | 18 | 0 | 30 | |||||||
| 71 | Slovakia | 18 | 0 | 10 | |||||||
| 72 | Austria | 18 | 0 | 48 | |||||||
| 73 | Latvia | 18 | 0 | 13 | |||||||
| 74 | New Zealand | 16 | 0 | 70 | |||||||
| 75 | Norway | 10 | 0 | 38 | |||||||
| 76 | Iceland | 7 | 0 | 35 |
Most water-stressed hubs
Pillars & weights
- Scarcity
- 25 %
- Future (2050)
- 15 %
- Seasonality & peaks
- 15 %
- Drought & groundwater
- 10 %
- Cooling demand
- 15 %
- Local competition
- 10 %
- Social & regulatory
- 10 %
Pressure = six physical pillars; index adds the social & regulatory pillar. Cooling source: NASA POWER daily 2015–2024 + WorldClim CMIP6 2041–2060 (pattern-scaled delta).
Distribution of data centers
Validation: the physical pressure score alone ranks the 167 data centers within 25 km of a documented water conflict above the others with ROC-AUC 0.662, over 6,687 scored data centers. It uses the 24 water cases located at a site or town (of those in the conflict atlas; cases located only at country or region level can't be tested), a small sample. Caveat: once spatial clustering is accounted for (resampling whole 5° cells) the interval is 0.49–0.804, which includes 0.5, so this test can't rule out chance. Spatial check →
Pillar sources
| Scarcity | WRI Aqueduct 4.0 baseline water stress and depletion (CC BY 4.0). |
| Future (2050) | Aqueduct 4.0 water stress 2050, business-as-usual scenario. |
| Seasonality & peaks | Aqueduct 4.0 monthly water stress (worst month, months at high stress) and seasonal variability. |
| Drought & groundwater | Aqueduct 4.0 drought risk, interannual variability and groundwater table decline (where modelled). |
| Cooling demand | Cooling degree days today and in 2050 and design wet-bulb temperature, hotter, more humid sites need more (often evaporative) cooling. |
| Local competition | Residents within 5 km (JRC GHSL 2020, CC BY 4.0), people sharing the same local supply. |
| Social & regulatory | Aqueduct reputational water risk and electric-power-weighted water risk, plus documented water conflicts within 50 km (Conflict atlas). |
Method: full method (v0.2, 2026-10-12). Related: social friction index · conflict atlas. Licence CC BY 4.0. Cite: Datacenter Atlas (2026). Water stress index for data centers, v0.2. https://www.datacenter-atlas.com/water